Automation & Control

Control, monitoring and interlocking engineered around your power system.

From agreed control philosophy to documented logic and interfaces.

Two matching monitors showing a substation single-line overview, event log and operating trends

Power automation capabilities

ATS & Main-Tie-Main

Transfer logic, operating sequences and interlocking.

Substation SCADA & ECMS

Monitoring, alarm handling and electrical system interfaces.

Power Management & Load Shedding

Control strategies linked to network operating scenarios.

Legacy PLC Migration

Recover existing logic and engineer the replacement.

Engineering that connects the system
I/O schedules
Logic diagrams
Interface mappings
Test documentation

Implementation and site support follow the agreed scope.

In detail: what the work covers

ATS & Main-Tie-Main Control Schemes

A standard two-source transfer is usually handled by a dedicated controller — Deep Sea, Socomec or ABB TruONE — and often needs nothing more. We work on the schemes those controllers are not designed for: multi-source, multi-tie arrangements with priority logic, synchronism check and pre-transfer load shedding, where the consultant specification mandates a programmable controller communicating to SCADA or BMS.

What this covers

  • Main-Tie-Main (3-in-2) — open, closed and fast transition with bus dead-time grading and priority return.
  • Multi-source and multi-tie logic — 4-in-2 and 3-in-1 arrangements across utility feeds, standby generators and segmented essential/non-essential busbars.
  • Synchronism check (ANSI 25) and parallel-transition blocking, so that sources which must not be paralleled are blocked from closing together.
  • Generator sequencing — start/stop scheduling, run-on and cool-down cycles, and load acceptance steps.
  • Pre-transfer load tripping — shedding non-essential feeders before the bus-tie closes, to avoid overloading a single transformer or generator on transfer.
  • Control circuit integrity — anti-pumping, trip circuit supervision, DC supply monitoring and breaker position discrepancy alarms.
  • Operator interface — dynamic single-line mimic, source health status, auto/manual override, adjustable transfer timers and alarm history.

Standards and references

Transfer schemes are engineered to IEC 60947-6-1 for transfer switching equipment and IEC 61131-3 for control logic, with synchronism check following the applicable IEEE C37 practice and the project's transfer timing and interlocking specification.

The same team calculates your fault levels and sets your relays. Automation logic that has to interact with protection is written by people who understand both sides of it.

Logic is verified in simulation against the agreed operating and failure scenarios and demonstrated in a virtual FAT before hardware is assembled. Panel and site tests then complete the verification.

ATS Circuit Design

Automatic Transfer Switch schemes decide what happens to your critical loads in the seconds after a supply is lost. We design them three ways — as hardwired logic, configured inside numerical relays, or on dedicated PLC control — and recommend the one that matches your availability requirement and maintenance capability, not the one that suits a particular supplier.

What this covers

  • Transfer scheme selection — open, closed and fast transfer, with the trade-offs made explicit for your load types.
  • Implementation route — hardwired relay logic, logic internal to numerical relays, or PLC-based control.
  • Supply supervision — undervoltage, phase loss, phase sequence and synchronism check criteria.
  • Motor load considerations — residual voltage decay and re-acceleration behaviour on transfer.
  • Interlocking — preventing parallel operation of sources that must not be paralleled.
  • Architecture — conventional hardwired signalling or IEC 61850 GOOSE, including transfer timing implications.

Standards and references

Design references IEC 61850 where a station bus is used, IEC 60255 for relay functions, and the IEEE C37 series for transfer scheme practice.

Power Management Systems & Fast Load Shedding

When an islanded plant loses its utility tie or a gas turbine trips, non-essential load may have to be shed within tens of milliseconds to keep the captive grid stable. Which feeders are shed, in what order, and on what trigger is a power system question before it is a programming one — which is why it is engineered together with the power system studies.

What this covers

  • Dynamic contingency calculation — continuous comparison of spinning reserve against operating load, so the shedding table reflects the plant's actual running configuration.
  • Fast load shedding — priority-table feeder tripping, with the required response time set in the design specification and checked in testing.
  • Under-frequency and under-voltage staged shedding as the fallback layer when fast shedding is insufficient or unavailable.
  • Active and reactive power sharing — dispatch to generator governors and AVRs to balance load and hold bus voltage.
  • Redundant architecture — S7-1500H redundant CPUs with ET 200SP distributed I/O over fault-tolerant Profinet (MRP) rings.
  • Interaction with protection — defining which protection trips initiate shedding and, just as importantly, which must not.

Standards and references

Contingency cases are derived from load flow and stability studies prepared to IEEE 399 and IEEE 1110, with control logic to IEC 61131-3 and redundant Ethernet to IEC 62439 (MRP).

The same team calculates your fault levels and sets your relays. Automation logic that has to interact with protection is written by people who understand both sides of it.

Logic is verified in simulation against the agreed operating and failure scenarios and demonstrated in a virtual FAT before hardware is assembled. Panel and site tests then complete the verification.

Substation SCADA & Electrical Control and Monitoring Systems

An Electrical Control and Monitoring System pulls your numerical relays, power meters and transformer controllers into one workstation and presents them as a live single-line diagram. The engineering difficulty is rarely the graphics — it is knowing what the relay data objects actually mean and which alarms matter.

What this covers

  • Profinet and OPC UA integration upstream to plant DCS and building management systems.
  • Animated single-line mimic — breaker state (closed, open, tripped, racked out, earth switch closed), voltage, active and reactive power, and power factor.
  • Sequence of Events logging at millisecond resolution with SNTP time synchronisation, so a cascading trip can be reconstructed in order.
  • Power quality reporting — THD monitoring, load duration trends and energy consumption logs.
  • Network architecture — segmentation, redundancy and the communication point schedule.

Standards and references

Communications are engineered to IEC 61850 for substation data and the relevant Modbus and Profinet specifications, with network segmentation reviewed against IEC 62443 principles for industrial control system security.

The same team calculates your fault levels and sets your relays. Automation logic that has to interact with protection is written by people who understand both sides of it.

Logic is verified in simulation against the agreed operating and failure scenarios and demonstrated in a virtual FAT before hardware is assembled. Panel and site tests then complete the verification.

Legacy PLC Migration & Retrofit

Legacy S7-200, S7-300, S7-400 and Moeller or Telemecanique controllers reach a point where spares dry up and the original programmer is long gone. The risk in these projects is rarely the conversion itself — it is the undocumented logic nobody can explain, which is why the audit comes before anything is rewritten.

What this covers

  • Code audit — reading and documenting existing STEP 7 v5.x logic, including the blocks nobody has touched in fifteen years.
  • Block conversion — STL and LAD blocks and data blocks rebuilt in TIA Portal SCL and LAD rather than machine-translated.
  • Network migration — Profibus-DP to Profinet planning, bridging where a staged cutover is needed.
  • HMI redesign — obsolete WinCC flexible panels rebuilt in WinCC Unified or Basic.
  • Schematic update — revised terminal assignments, 24 VDC control distribution and terminal block layouts.
  • Staged changeover — sequencing planned to keep the switchboard in service where practicable, with fallback at each step.

Standards and references

Converted logic is structured to IEC 61131-3, with network migration to the applicable Profinet and Profibus specifications and schematics to IEC 81346 reference designation practice.

The same team calculates your fault levels and sets your relays. Automation logic that has to interact with protection is written by people who understand both sides of it.

Logic is verified in simulation against the agreed operating and failure scenarios and demonstrated in a virtual FAT before hardware is assembled. Panel and site tests then complete the verification.

Define your control and monitoring requirements.

Discuss Your Automation Project