ATS & Main-Tie-Main Control Schemes

A standard two-source transfer is handled by a dedicated controller — Deep Sea, Socomec or ABB TruONE — and there is no engineering case for anything more. We work on the schemes those controllers cannot do: multi-source, multi-tie arrangements with priority logic, synchronism check and pre-transfer load shedding, where the consultant specification mandates a programmable controller communicating to SCADA or BMS.

What this covers

  • Main-Tie-Main (3-in-2) — open, closed and fast transition with bus dead-time grading and priority return.
  • Multi-source and multi-tie logic — 4-in-2 and 3-in-1 arrangements across utility feeds, standby generators and segmented essential/non-essential busbars.
  • Synchronism check (ANSI 25) and parallel-transition blocking, so two sources that must never be paralleled cannot be.
  • Generator sequencing — start/stop scheduling, run-on and cool-down cycles, and load acceptance steps.
  • Pre-transfer load tripping — shedding non-essential feeders before the bus-tie closes, so a single transformer or generator is not overloaded on transfer.
  • Control circuit integrity — anti-pumping, trip circuit supervision, DC supply monitoring and breaker position discrepancy alarms.
  • Operator interface — dynamic single-line mimic, source health status, auto/manual override, adjustable transfer timers and alarm history.

What you receive

  • TIA Portal application (.zap archive) in structured LAD and SCL with IEC-compliant tagging
  • KTP-series HMI project with the mimic, override and timer screens
  • Control philosophy document and cause-and-effect / trip matrix
  • S7-PLCSIM simulation record covering every transfer case and failure mode
  • PLC I/O assignment schedule cross-referenced to the panel schematics

Standards and references

Transfer schemes are engineered to IEC 60947-6-1 for transfer switching equipment and IEC 61131-3 for control logic, with synchronism check following the applicable IEEE C37 practice and the project's transfer timing and interlocking specification.

Related services

Substation SCADA & ECMS

A monitoring layer over your MV and LV network that operators can actually act on.

Power Management & Fast Load Shedding

Dropping the right load in milliseconds, before the captive grid collapses.

Legacy PLC Migration & Retrofit

Moving obsolete switchboard controllers to current platforms without losing the logic.

All RelaNex Group services →

Need this scoped?

Tell us about the switchboard, the source configuration and the specification you have been handed.

Get in Touch